| Technical data | BK5120 |
|---|---|
| Number of Bus Terminals | 64 (255 with K-bus extension) |
| Max. number of bytes fieldbus | 16 Tx/Rx PDOs |
| Digital peripheral signals | 960 inputs/outputs |
| Analog peripheral signals | 60 inputs/outputs |
| Configuration possibility | via KS2000 or the controller |
| Number of PDOs (CANopen) | 16 Tx/16 Rx |
| Additional CANopen features | life, node guarding, emergency object, variable mapping, store/restore |
| Data transfer rates | up to 1 Mbaud |
| Bus interface | 1 x open style connector, 5-pin, included |
| Power supply | 24 V DC (-15 %/+20 %) |
| Input current | 70 mA + (total K-bus current)/4, 500 mA max. |
| Starting current | approx. 2.5 x continuous current |
| Recommended fuse | ≤ 10 A |
| Current supply K-bus | 1750 mA |
| Power contacts | max. 24 V DC/max. 10 A |
| Electrical isolation | 500 V (power contact/supply voltage Bus Coupler) |
| Weight | approx. 150 g |
| Operating/storage temperature | -25…+60 °C/-40…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, UL, ATEX, DNV GL |
| Ex marking | II 3 G Ex nA IIC T4 Gc |